Search This Blog

Thursday, 24 November 2016

Zig Zag Transformer

ZIg Zag transformer is a special purpose transformer used in power system, which is also called as “interconnected start winding”. Even though this type of transformer connection is not useful in transforming power, it has many features combining Star and Delta type winding connections.

Zig Zag transformer winding connections

 Zig Zag transformer has six coils in which three are outer coils and three are inner coils as shown in the figure. The outer coil windings are called as ZIG winding and inner coil windings are connected as ZAG winding. The zig winding of one phase is connected in series with the zag winding of another phase so it is called interconnected star winding where two star winding coils are interconnected each other.  In each phase two coil windings will have same number of turns but they are wounded in opposite directions to cancel the mismatch voltages. Following are the connections of zig zag winding coils.Image result for zig zag connection of transformer

 

1) The outer coil of phase ‘a’ is connected with the inner coil of phase ‘b’
1) The outer coil of phase ‘b’ is connected with the inner coil of phase ‘c’
1) The outer coil of phase ‘c’ is connected with the inner coil of phase ‘c’

The inner coil second terminals are connected together and connected to neutral terminal to pass the zero sequence current components.

The interconnection of winding of different phases introduces 30 phase shift between zig winding and the corresponding line to neutral voltage. The zig-zag winding have 15.47% more turns compared to conventional transformers to get the same magnitude of voltages. Hence the cost of zig zag transformer is high and it is essential in some applications to be used.

Zig Zag Transformer applications or uses

Grounding Transformer

It can be used as earthing transformer in a delta connected (no neutral terminal) system or an ungrounded start connected (three terminal star) where in neutral is not available for grounding. The zig zag transformer used for earthing of delta connected transformer.

In delta connected transformer there will not be path to zero sequence components and no protection can be performed for these components which increases and stress and heating in the windings. The zig zag transformer provides a neutral for the proving a path to zero sequence components during line to ground fault and allows the protection to be operated due to this fault. In the obsence of grounded neutral, voltages of healthy would increase line to line voltage level, stressing the insulation connected to equipment. Thug Zig zag transformer not only helps in protection it also reduces the voltages stress under symmetrical fault conditions.

2) Power Electronic converters

In power electronic converters the zig zag transformer is used to eliminate the DC magnetizing component presented due to improper firing angles. The improper firing angles of power electronic components (SCR) may introduce DC magnetizing component and this is canceled in each limb of zig zag transformer due to opposite direction of DC magnetizing component of currents flowing in the windings on the same limb.

3) Earthing reference or earthing transformer

Zig zag transformer offers low impedance path to zero sequence components under fault conditions so it can be perfectly used as earthing transformer with and earthing reference. If the earthing current has to be limited under fault conditions, a suitable resistor can be placed in zig zag neutral terminal.

4) Harmonic voltages presented in system to some extent can be cancelled in zigzag windings due to opposite connection of winding coils.

Advantage of Zig zag transformer

The following are the advantages of zigzag transformer compared to Scott transformer and other grounding transformers
  1. Less cost compared to Scott transformer
  2. Provides low impedance to zero sequence currents
  3.  Harmonic voltages suppression
  4. It provides perfect isolation between ground and component
 

 


Tuesday, 25 October 2016

Difference between LDR and Photodiode

The use of photosensors is increasingly being used in the world today in many innovations, using the basic principle of using light for sensing. A good example of photo sensors in use is the line-following robot, which will makes use of this unique invention. Any project that needs to employ the use of photo sensors must decide on the specific type of invention to use. There are two commonly used types of photo sensors and these are the Light Dependent Resistor (commonly abbreviated LDR) and the photodiode. What specific differences do these two photosensors have and what dictates regarding the type of sensor to use? The specific properties of each sensor are the main dictator of where and when they can be used.

The Light Dependent Resistor (LDR) is one of the most widely used and preferred photo resistor in most projects that requires the use of a photosensor. The most ideal characteristic it carries is that it is cheap and rugged. This means it can be used in multiple projects. Also, as the name of LDR denotes, their resistance to electricity depends on the intensity of light shining on them. It can thus be said that their resistance is inversely proportional to the amount of light they receive. LDR are therefore the most preferred photosensors, whereby a varying amount of light intensity is expected, as opposed to a light intensity that is fixed.

The LDR is also preferred as the sensor of choice when a hardy build is required. This is especially the case when the sensor is expected to operate in a hardy and rough environment. The response time of LDR is moderate and it is also advantageous, as it is a bidirectional resistor.

The photodiode in itself comes with a quick response time and if the build incorporates fast responses, them the photodiode is the appropriate choice to make use of. The cost of the photodiode is also low, just as that of the LDR. Contrary to use of LDR in varying intensities of light, the photodiode is mainly used in the reverse bias, turning off when a certain light intensity is exceeded. This means that the photodiode has specifically two levels of output. Either it is off when the light intensity is exceeded or on when the light intensity is adequate. The use of the photodiode is therefore preferred in environments where there is need to keep check of the light intensities. From the action of the photodiode, it can be said to be unidirectional in nature.

In applications, the LDR can function well when used in street lighting circuits, as it will measure the varying light intensities and switch the lights on when a certain threshold is met. On the other hand, photodiodes are preferred to be used in precision equipment such as laboratory equipment, which is very specific. Use of the photodiode will therefore be seen in instruments like the spectrometer, analyzers and other digital precision circuits

Separately Excited Generator

When the field winding is supplied from external, separate d.c. supply i.e. excitation of field winding is separate then the generator is called separately excited generator. Schematic representation of this type is shown in the Fig.1.
Fig. 1  Separately excited generator
       The field winding of this type of generator has large number of turns of thin wire. So length of such winding is more with less cross-sectional area. So resistance of this field winding is high in order to limit the field current.
 
  Voltage and Current Relations :

       The field winding is excited separately, so the field current depends on supply voltage and resistance of the field winding. 
       For armature side, we can see that it is supplying a load, demanding a load current of IL at a voltage of Vt which is called terminal voltage.
       Now   Ia = IL
       The internally induced e.m.f. E is supplying the voltage of the load hence terminal voltage Vt is a part of E. But E is not equal to Vt while supplying a load. This is because when armature current Ia flows through armature winding, due to armature winding resistance Ra ohms, there is a voltage drop across armature winding equal to Ia Ra volts. The induced e.m.f. has to supply this drop, along with the terminal voltage Vt. To keep Ia Ra drop to minimum, the resistance  Ra is designed to be very very small. In addition to this drop, there is some voltage drop at the contacts of the brush called brush contact drop. But this drop is negligible and hence generally neglected. So in all, induced e.m.f. E has three components namely,
 
i) Terminal voltage Vt
ii) Armature resistance drop  Ia Ra
iii) Brush contact drop Vbrush 
 
       So voltage equation for separately excited generator can be written as,
       E = Vt + Ia Ra + Vbrush
       Where E = (ΦPNZ)/(60A)
       Generally Vbrush  is neglected as is negligible compared to other voltages.

Types of DC Generator

1. Separately Excited Generator :
 In a separately excited DC generator, the field winding is excited by an external independent source.

2. Self Excited DC Generator. These are generators in which the field winding is excited by the output of the generator itself. As described before – there are three types of self excited dc generators – they are 1) Series 2) Shunt and 3) Compound.
Q. What is Residual Magnesium?
Q. What is armature reaction in DC Generator ?
Q. What is the reason of the generated emf reduce while increase the load current ?

Brushes Used in DC Generator

Q.Why is carbon used in the brushes in a DC generator?
The inductances of the energized windings, and the mechanics of a brush type motor or generator make arcing and sparking an unavoidable characteristic of the machine at the brush interface. Electrical arcs produce very high temperatures. High enough to melt metals. 

Voltage drop across brushes is 1-2 volts

 

Carbon has a very high melting point (~3500degC) compared with other conductors. Brushes made with copper or steel would wear out faster because of factors including:


1) The melted metal will break away from, or even be vaporized, leaving the brush with less material to do its job.
2) If the melted material doesn't vaporize or otherwise move away from the interface, it creates a mess for the brush. It can weld together bristles of the brush. It can build up material that interferes with the motion of the rotor.
3) As the metal melts in the presence of an arc, conductive material can be liberated, therby prolonging the arc, exasperating the wearing action.

Carbon is less prone to those high temperature effects and associated impacts to the generator operation.
Also, Graphite is conductive and auto-lubricant (low friction coefficient) so, it provides a good dynamic contact to rings with minimum erosion. 


Carbon Graphite - Carbon Graphite brushes have been used in motor applications since the use of actual copper wire brushes that wore away the commutator. This material is mainly used as a base for impregnating metal graphite brushes today. Carbon graphite can be used in lower current density and lower speed applications because of its high resistivity.

Electrographitic – Electrographitic brushes are baked in excess of 2000°C to increase the strength of the material. These can stand up to very high current densities and high speed applications. With a lower resistance, electrographitic brush grades can also tolerate higher temperatures. There are many different grades in this material and it is the most widely used brush on the market today.

Graphite – Graphite brushes are available in several grades with different resistances and strengths needed for specific applications, such as high speed turbo generators and slip ring motors. Generally low to medium current density and lower speed applications use this grade as a cheaper alternative to electrographitic or metal graphite brushes.

Metal Graphite – Metal graphite brushes offer very low resistance and high current density which means a much lower voltage drop across the brush. These are used commonly in low voltage machines that require these specifications such as DC motors, low voltage generators, and slip ring inductions motors. The low resistance also offers less EMI (electromagnetic interference) if that may be a problem for a particular industrial application around sensitive equipment.
 

Monday, 24 October 2016

Basic Working Principle of DC Generator

  • A DC generator operate on the principle of Dynamic induced emf explain by fleming right hand rule
  • Fleming's right-hand rule :  (for generators) shows the direction of induced current when a conductor moves in a magnetic field. It can be used to determine the direction of current in a generator's windings.

  • Induced emf in generator : e=B*l*v*sinθ, Here the induced emf is in form of Sine, so generated emf in DC generator is AC instead of DC. To convert in unidirectional DC signal use rectifying as Commutator.

DC Generator

Thursday, 18 August 2016

Que-Ans of DC Generator

  1. Q. What is Residual Magnesium?
  2. Q. What is armature reaction in DC Generator ?
  3. Q. What is the reason of the generated emf reduce while increase the load current ? 
  4. Q. At no load what is relation between Ideal and practical characteristics ? Why ?  
  5. Q. What is the value of field winding resistance ? Why is So ?
  6. Q. What is reason to fail DC Generator as self excite ?
  7. Q. If load of Dc Generator is disconnect, what is effect on induced emf  ?